Convert Amps (A) to kilovolt-Amps (KVA) Calculation
To convert Amps to KVA , Please provide the values below:
To calculate Amps to Volt-Amps Single phase, use the following formula:
The apparent power S in volt-amps (KVA) is equal to the voltage V in volt (V) times the current I in amps (A), divided by 1000.
To calculate Amps to Volt-Amps Three phase line to line voltage, use the following formula:
The apparent power S in volt-amps (KVA) is equal to √3 times the line to line voltage V in volt (V) times the current I in amps (A), divided by 1000.
To calculate Amps to Volt-Amps Three phase line to neutral voltage, use the following formula:
The apparent power S in volt-amps (KVA) is equal to 3 times the line to neutral voltage V in volt (V) times the current I in amps (A), divided by 1000.
For Example 01
If an Induction motor takes single phase 230V, 1.2A power at 0.99 (lag) power factor from the AC source and runing time 6 hours. Calculate the kilovolt-amps (KVA) of the motor.
Answer
Where,
V = 230V , I = 1.2A , Pf = 0.99,T = 6 hours
We Know
S (KVA) = V(V) x I(A) ÷1000
S (KVA) = 230 x 1.2÷1000
S (KVA) = 0.276
KVA = 0.276
For Example 02
If an Induction motor takes Three phase Lime to Line voltage 400V, 2.2A power at 0.99 (lag) power factor from the AC source and runing time 6 hours. Calculate the kilovolt-amps (KVA) of the motor.
Answer
Where,
V = 400V , I = 2.2A , Pf = 0.99,T = 6 hours
We Know
S (KVA) = √3 x V(V) x I(A)÷1000
S (KVA) = √3 x 400 x 2.2÷1000
S (KVA) = 1.524
KVA = 1.524
For Example 03
If an Induction motor takes Three phase Lime to neutral voltage 380V, 5A power at 0.99 (lag) power factor from the AC source and runing time 6 hours. Calculate the kilovolt-amps (KVA) of the motor.
Answer
Where,
V =380V , I = 5A ,Pf = 0.99,T = 6 hours
We Know
S (KVA) = 3 x V(V) x I(A)÷ 1000
S (KVA) = 3 x 380 x 5÷1000
S (KVA) = 5.7
KVA = 5.7
See Also:
Advertisements
$ads={2}
Power Factor Value conversion table | ||
---|---|---|
SL No | Device | Typical PF |
01 | Synchronous Motor | 0.9 |
02 | Induction Motor full load | 0.85 |
03 | Induction Motor no Load | 0.35 |
04 | Fluorescent Lamp | 0.95 |
05 | Resistive Oven | 1 |
06 | Resistive Load | 1 |
07 | Incandescent Lamp | 1 |
Do not use normal power factor values for exact calculations
Single phase Amps to Kilovolt-amps and Voltage Table:
Single phase Amps to Kilovolt-amps with Voltage Table: |
|||
---|---|---|---|
SL No | Amps (A) |
Voltage (V) |
Kilovolt-amps (KVA) |
01 | 2 | 180 | 0.36 |
02 | 3 | 180 | 0.54 |
03 | 4 | 180 | 0.72 |
04 | 5 | 180 | 0.90 |
05 | 6 | 180 | 1.14 |
06 | 7 | 190 | 1.33 |
07 | 8 | 190 | 1.52 |
08 | 9 | 190 | 1.71 |
09 | 10 | 190 | 1.90 |
10 | 2 | 190 | 0.38 |
11 | 3 | 200 | 0.60 |
12 | 4 | 200 | 0.80 |
13 | 5 | 200 | 1.00 |
14 | 6 | 200 | 1.20 |
15 | 7 | 200 | 1.54 |
16 | 8 | 220 | 1.76 |
17 | 9 | 220 | 1.98 |
18 | 10 | 220 | 2.20 |
19 | 11 | 220 | 2.42 |
20 | 12 | 220 | 2.64 |
Three phase Amps to Kilovolt-amps (KVA) and line to line Voltage Table:
Three phase Amps to Kilovolt-amps (KVA) with line to line Voltage Table: |
|||
---|---|---|---|
SL No | Amps (A) |
Voltage (V) |
kilovolt-amps (KVA) |
01 | 2 | 380 | 1.316 |
02 | 3 | 380 | 1.974 |
03 | 4 | 380 | 2.632 |
04 | 5 | 380 | 3.290 |
05 | 6 | 380 | 3.948 |
06 | 7 | 390 | 4.728 |
07 | 8 | 390 | 5.403 |
08 | 9 | 390 | 6.079 |
09 | 10 | 390 | 6.754 |
10 | 2 | 390 | 1.350 |
11 | 3 | 400 | 2.078 |
12 | 4 | 400 | 2.771 |
13 | 5 | 400 | 3.464 |
14 | 6 | 400 | 4.156 |
15 | 7 | 400 | 4.849 |
16 | 8 | 400 | 5.542 |
17 | 9 | 400 | 6.235 |
18 | 10 | 400 | 6.928 |
19 | 11 | 400 | 7.620 |
20 | 12 | 400 | 8.313 |
Three phase Amps to kilovolt-amps (KVA) and line to neutral Voltage Table:
Three phase Amps to kilovolt-amps (KVA) with line to neutral Voltage Table: |
|||
---|---|---|---|
SL No | Amps (A) |
Voltage (V) |
Kilovolt-amps (KVA) |
01 | 2 | 380 | 2.280 |
02 | 3 | 380 | 3.420 |
03 | 4 | 380 | 4.560 |
04 | 5 | 380 | 5.700 |
05 | 6 | 380 | 6.840 |
06 | 7 | 390 | 8.190 |
07 | 8 | 390 | 9.360 |
08 | 9 | 390 | 10.530 |
09 | 10 | 390 | 11.700 |
10 | 2 | 390 | 2.340 |
11 | 3 | 400 | 3.600 |
12 | 4 | 400 | 4.800 |
13 | 5 | 400 | 6.000 |
14 | 6 | 400 | 7.200 |
15 | 7 | 400 | 8.400 |
16 | 8 | 400 | 9.600 |
17 | 9 | 400 | 10.800 |
18 | 10 | 400 | 12.000 |
19 | 11 | 400 | 13.200 |
20 | 12 | 400 | 14.400 |
Frequently Asked Questions:
What do you convert single phase Amps to kilovolts-amps (KVA) for ?
One Amps is equal to 0.230 Kilovolt-amps (KVA) for voltage 230V
What is AC Circuit single phase 10 amps 210 volts in kilovolts-amps (KVA) ?
2.10 kilovolts-amps (KVA)
What do you convert three phase Amps to kilovolts-amps (KVA) for ?
One Amps is equal to 69.282 kilovolts-amps (KVA) for line to line voltage 400V
What is AC Circuit three phase 10 amps 380V Line to line voltage in kilovolts-amps (KVA) ?
6.581 kilovolts-amps (KVA)
What is single phase the formula for amps to kilovolts-amps (KVA) ?
Apparent Power (KVA) = Amps (A) x Voltage (V) ÷ 1000
What is three phase , line to line voltage the formula for amps to kilovolts-amps (KVA) ?
Apparent Power (KVA) = √3 x Amps (A) x Voltage (V) ÷ 1000
What is three phase , line to neutral voltage the formula for amps to kilovolts-amps (KVA) ?
Apparent Power (KVA) = 3 x Amps (A) x Voltage (V) ÷ 1000
If 15 amps,230V,single phase , how much is kilovolts-amps (KVA) ?
3.450 kilovolts-amps (KVA)
If 15 amps,410 V,three phase , how much is kilovolts-amps (KVA) ?
10.652 kilovolts-amps (KVA)
If 3 amps,400V,three phase , how much is kilovolts-amps (KVA) ?
2.078 kilovolts-amps (KVA)
You may like these posts:
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEgCfXN9GIGrpvsIDn1h0TxmPRnfvir5EJFLuJeqtymRJ_4QvXUOm2UFyQQ5axPjXgBrvh2gAv7YsLbgomvOA46RJHCkswPAqWcbAsNgU-dEXKgGaZmNFWe9MrhxRHCGJ03FlQqGaZBjWUffoxHdjCXekIfVwof_fkoIzYIRyZYrr7f5dA/s1600-rw/arduino-hardware.webp)
24V Negative Voltage Regulator power supply. This is the circuit diagram. In this circuit, an input negative voltage of -28V is used.
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEg0BJ5gJObzEYpQdE0TjO03PUQ7rU6WAFxcCKdFSMqd4hCYqX97HdWgWRQA_PAGTxyg0Fkt3SfBT9Uwb1mkVs3i_AaJj1E0tgdh-Kfq_LPFQqyq50BIz9RjjZ2UKCVZzeaslDDa4lewH0lZray2vb8V-pSxxuZ8TlcVhFx93O8e5WNIiA/s1600-rw/5v-12amp-short-ckt-protection-diagram.webp)
24V Negative Voltage Regulator power supply. This is the circuit diagram. In this circuit, an input negative voltage of -28V is used.
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEh-kSQ2M5BWeYCrBU64vMue7qH7wz6mEjx9lHyvQIQVNWrzz4hE8JXdLnXDxqLqhQeNVH_6G7Zc5SgM5aMJP-J_2pL7Y-_QKNpC_xmhW6Hf1zg3GDzNoF3KQ5b9-RsFEA7Fgz0oGeEwEdeUh1629_J_EJlxIds-VZ9Dne1LvspWtezKUA/s1600-rw/kwatt-hrs-to-kw-calculation.webp)
Convert kilowattshours (KWh) to Kilo-Watts (KW) Calculation
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEgLjWkhT9j_w0bG3fBP-svKOr-SUWn5PslYpTaAiCFSXTjRGRBEUjzhzfHmCNIwm84wrv47pS5L-dwiIjCUKfbyKw5BsHOUcJP678Ny5wqObrxF57ljB_cfTe4WRefn-rS3vK4Tay_OfohO-VCgyT2CJIHotmEH8kY2wwBSVPJrzBCYAg/s1600-rw/watt-to-kwatt-hours-calculation.webp)
Convert Watts (w) to kilowattshours (KWh) Calculation
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEj2PzI1cJM31JAiFOl46vAdlOT33oRlxcByT_g03Glzp4diX6ty7Z0Xrmo4dFgGz_dOVqTKtTTTxXpsRlpA_2kky2bjVW1rDh1jwtIrLwbK_AF4sIAEllLefhJjFT0OFs9c7skoh__2FLqnnY-Jl3wg9yD3_UbCQAHCRHa75Y4a3ZrsYA/s1600-rw/kwatt-hours-to-watts-calculation.webp)
Convert kilowattshours (KWh) to Watts (W) Calculation
![](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEg0BJ5gJObzEYpQdE0TjO03PUQ7rU6WAFxcCKdFSMqd4hCYqX97HdWgWRQA_PAGTxyg0Fkt3SfBT9Uwb1mkVs3i_AaJj1E0tgdh-Kfq_LPFQqyq50BIz9RjjZ2UKCVZzeaslDDa4lewH0lZray2vb8V-pSxxuZ8TlcVhFx93O8e5WNIiA/s1600-rw/5v-12amp-short-ckt-protection-diagram.webp)
24V Negative Voltage Regulator power supply. This is the circuit diagram. In this circuit, an input negative voltage of -28V is used.
Post a Comment